Cleanroom Air Distribution Plenums – Uniform HEPA Supply for ISO & GMP | Metrolabs Chennai
📍 Chennai, Tamil Nadu | Pan India 📞 9840931231 ✉ metrolabs1@gmail.com
Home Cleanroom Home HVAC & Air Handling Air Distribution Plenums
Pressurised Equalising Chamber · ISO 14644 · GMP · Uniform HEPA Supply

Cleanroom Air Distribution Plenums — The Equalising Chamber for Uniform HEPA Supply

A terminal HEPA filter is only as effective as the air pressure driving air through it. Without a correctly designed pressurised plenum above the cleanroom ceiling, the HEPA units nearest the AHU supply connection receive higher static pressure and higher airflow than those furthest away — creating velocity imbalances, dead zones, and ISO class failures at the remote end of the cleanroom. Metrolabs Air Distribution Plenums are purpose-designed pressurised chambers above the cleanroom ceiling grid that equalise static pressure across every HEPA position, ensuring that every terminal filter delivers the same velocity of clean air regardless of its distance from the AHU connection.

GI / Aluminium / SS Sealed Airtight Uniform Static Pressure FFU Compatible Walkable Access ISO 14644 Compliant
Plenum Quick-Reference
Primary FunctionEqualise static pressure to all HEPAs
Casing MaterialGI / Aluminium / SS 304
Sealing StandardAirtight — SMACNA Class A joints
HEPA InterfaceGel-seal / gasket housing receptacles
FFU CompatibilityFan Filter Units — recirculating plenum
AccessWalkable top skin / access hatches
⚖️
Zero dead
zones in room
GMP ISO
Compliant
📍
Pan-India
Install
⚖️
Equalises Static Pressure — Zero Dead Zones
🌐
Uniform Velocity to Every HEPA Position
🔒
Airtight Sealed — SMACNA Class A
💨
FFU Recirculating & Ducted Supply Options
🔧
Walkable Access — Maintenance & Cleaning
ISO 14644 / GMP / NABL Compliant
Air Distribution Plenum — Pressure Equalisation Cross-Section
STRUCTURAL CEILING / ROOF SLAB PRESSURISED AIR DISTRIBUTION PLENUM Equalised static pressure across all HEPA positions AHU SUPPLY Uniform static pressure field throughout plenum volume CLEANROOM CEILING GRID H14 HEPA #1 H14 HEPA #2 H14 HEPA #3 0.45 m/s 0.45 m/s 0.45 m/s Equal velocity from all HEPA positions — no dead zones CLEANROOM ISO Class 3–8 · Grade A–D RISER RISER WITHOUT PLENUM 0.72 0.18 Velocity imbalance — dead zone 25 Pa positive pressure throughout
⚖️ Pressure Equalisation
Single AHU duct connection. Plenum distributes equal static pressure to every HEPA position.
🌐 Zero Velocity Imbalance
Every H14 HEPA delivers 0.45 m/s — regardless of distance from AHU supply connection.
🔒 Airtight Sealed Chamber
SMACNA Class A sealed joints. Controlled positive pressure throughout the plenum volume.
🔧 Walkable Access
Reinforced top skin allows maintenance access to FFU modules, lighting, and sprinklers above.
The Pressurised Equalising Chamber

What a Plenum Does That Direct Ducting Cannot

Without a plenum, supplying air to twelve HEPA filters through a single AHU duct connection creates a severe static pressure gradient along the duct — the HEPA nearest the supply receives far more air than those at the far end. The plenum solves this by converting duct velocity pressure into uniform static pressure across the entire ceiling void.

⚖️

Pressure Equalisation — Every HEPA Receives Identical Static Pressure

When conditioned air from the AHU enters the plenum through the supply connection, its velocity energy is converted into static pressure uniformly distributed throughout the sealed plenum volume. Because the plenum is a closed, pressurised vessel — not a duct — Pascal’s law ensures that the static pressure is equal at every point within it — at the near HEPA housing and at the far HEPA housing alike. Each terminal HEPA filter then draws the same volume of air at the same face velocity, delivering identical laminar downflow across every position in the cleanroom ceiling.

🌐

Eliminating Dead Zones — No Velocity Imbalance

In a directly ducted system without a plenum, the HEPA filter closest to the AHU supply receives perhaps 0.72 m/s face velocity while the filter furthest away receives only 0.18 m/s — well below the 0.36 m/s minimum for Grade A laminar flow compliance. The low-velocity areas become dead zones where particles accumulate rather than being swept downward — creating localised ISO class failures within an otherwise compliant room. The plenum eliminates this velocity gradient entirely.

💨

Air Mixing — Uniform Temperature at Every HEPA

In a recirculating plenum, the return air from the cleanroom (carrying the heat load from personnel and equipment) mixes with the conditioned fresh air supply before re-entering the cleanroom through the terminal HEPA filters. This mixing eliminates the hot and cold spots that direct-ducted systems create — ensuring that the temperature entering through every HEPA position is uniform and that the T&H controller setpoint is achieved consistently across the entire room, not just near the supply.

🔧

Simplified Infrastructure — Reduced Installation Complexity

Instead of individual duct connections to every HEPA terminal housing (which requires an extensive duct branch network, individual volume control dampers, and time-consuming airflow balancing at commissioning), a plenum requires only a single AHU supply connection to the plenum body. The plenum itself handles the distribution — dramatically reducing the duct installation scope, the number of joints to seal and test, and the commissioning time for airflow balancing.

Plenum Types

Four Air Distribution Plenum Configurations

Metrolabs designs and fabricates four plenum configurations — each matched to a specific cleanroom scale, HVAC system type, and ISO class requirement:

🔌

Ducted Supply Plenum — AHU + Terminal HEPA

The standard pharmaceutical cleanroom plenum configuration. The AHU supplies conditioned and F9-pre-filtered air through GI ductwork to the plenum via one or two supply connections. The plenum body — fabricated from sealed, insulated GI panel or aluminium — distributes this supply air at uniform static pressure to each terminal H14 HEPA housing recessed into the cleanroom ceiling grid below. The AHU is sized for 100% of the room air change requirement — all conditioning (cooling, heating, humidity) is handled by the AHU. Preferred for pharmaceutical Grade A/B/C environments where single-zone HVAC control, individual room pressure management, and documented air balance are regulatory requirements. The ducted supply plenum is the primary choice where cross-room air mixing must be avoided.

AHU SupplyF9 Pre-FilteredIndividual RoomGMP Grade A–D
✓ Best for: Pharmaceutical, aseptic, ISO 5–8 individual room control
💨

Recirculating Plenum with Fan Filter Units (FFU)

The recirculating plenum allows return air from the cleanroom to rise back into the plenum void (via ceiling openings or return risers venting to the plenum), mix with the conditioned fresh air supplied by the AHU, and be re-driven through ceiling H14 HEPA filters into the cleanroom by individual Fan Filter Units (FFUs) mounted in the plenum. The FFU handles the fan energy for its own HEPA section — the AHU needs only to condition (cool, heat, humidify) the fresh air percentage, not the full recirculation volume. This dramatically reduces AHU fan size and energy consumption for high-ACH ISO Class 3–6 environments where air change rates of 200–600+ ACH would make a single AHU fan prohibitively large. Standard for semiconductor, ATMP, and electronics cleanrooms where energy efficiency at very high ACH is the design priority.

FFU RecirculatingHigh ACH (200–600+)Energy EfficientISO 3–6
✓ Best for: Semiconductor, ATMP, high-ACH ISO 3–6 cleanrooms
🏱

Modular Plenum — Segmented Multi-Room System

For multi-room pharmaceutical suites where different rooms require different air change rates, different ISO classes, or independent pressure control, the modular plenum system provides a separate plenum segment above each room — each fed by its own AHU branch connection with its own VCD to independently control the supply volume to each segment. Plenum segments are physically separated by sealed partition walls within the plenum void — preventing air from one plenum segment (above one room) from flowing into an adjacent segment (above another room). This eliminates any possibility of cross-room air contamination through the plenum void — a critical requirement for pharmaceutical facilities with adjacent rooms of different GMP grades or different product campaigns. Each segment commissions, balances, and validates independently.

Multi-RoomSegmentedIndependent ControlCross-Contamination Safe
✓ Best for: Multi-room pharma suites, mixed ISO class facilities
🌳

Hybrid Plenum — FFU ISO 5 within Ducted ISO 7

An innovative hybrid architecture increasingly adopted for pharmaceutical ATMP and biotech facilities — a recirculating FFU plenum providing ISO Class 5 (Grade A) laminar flow over the critical work zone, contained within a surrounding ISO Class 7 (Grade C) room maintained by a conventional ducted AHU supply. The outer room plenum uses a standard ducted AHU connection. The inner critical zone plenum uses FFUs with individual speed control to maintain the higher air change rate required for ISO Class 5 within the lower ACH outer environment. This eliminates the need to build a fully Grade A room around a small critical operation — achieving Grade A protection at the process point with Grade C infrastructure cost for the surrounding space. Widely used in filling lines, isolators with integrated Grade A overhead, and ATMP processing stations.

Hybrid FFU + DuctedISO 5 within ISO 7ATMP / FillingCost-Effective Grade A
✓ Best for: ATMP processing, filling lines, cleanroom-within-cleanroom
Engineering Design Features

Six Critical Engineering Features of Every Metrolabs Plenum

Every Metrolabs air distribution plenum is designed as a precision HVAC component — not a simple void — with six engineering features that determine ISO class performance:

🔒

Airtight Sealed Construction — SMACNA Class A

The plenum body is fabricated from GI sheet, aluminium sheet, or SS 304 panel with all joints formed using TDF flanges, sealant beads, and compressed gaskets — achieving SMACNA Class A air leakage performance throughout. Any leakage from the pressurised plenum directly reduces the static pressure available to drive air through the terminal HEPA filters, causing velocity imbalance and ACH shortfall. Every Metrolabs plenum is pressure-tested after installation to verify SMACNA Class A integrity before commissioning. Test records are included in the HVAC IQ documentation as evidence of plenum airtight performance.

TDF Flanged JointsSMACNA Class APressure TestedIQ Documented
🌟

HEPA Housing Receptacles — Gel-Seal or Gasket

The cleanroom ceiling-side of the plenum base incorporates the purpose-designed H14 HEPA terminal housing receptacles — either gel-seal channel type (mandatory for pharmaceutical Grade A/B) or EPDM gasket type (ISO Class 7–8). The receptacles are factory-fitted and sealed to the plenum base during plenum fabrication — ensuring the housing-to-plenum interface is as airtight as the plenum body itself. If air bypasses the HEPA filter through the housing-to-plenum seal, the filter’s classification efficiency is compromised regardless of the filter media grade. The gel-seal housing design eliminates bypass pathways completely.

Gel-Seal (Grade A/B)EPDM Gasket (Grade C/D)Factory Pre-FittedZero Bypass
🏽

Thermal Insulation — Condensation Prevention

The plenum body is insulated with 25mm closed-cell nitrile rubber or PIR board on the external (non-cleanroom) faces — preventing condensation on the cold plenum surface where the dew point of the warm ambient air outside the plenum meets the chilled surface of the plenum body. Condensation inside a plenum void creates standing water, microbial growth, and corrosion — all of which would contaminate the supply air entering the HEPA filters. Internal faces visible from within the plenum are finished smooth and non-porous — easily cleaned during planned maintenance access.

25mm Closed-Cell NBRPIR Board OptionNo CondensationSmooth Internal Finish
👉

Walkable Top Skin — Maintenance Access

For plenums that house Fan Filter Units, lighting, sprinkler heads, or other services, the top skin of the plenum is reinforced to provide a walkable surface — typically 3mm chequer-plate GI or aluminium — allowing maintenance personnel to walk on the plenum surface to access FFU modules, replace terminal HEPA filters from above (for top-load housings), and service any services installed above the ceiling grid without the need for scaffolding or mobile access equipment. Access hatches are positioned at regular intervals in the plenum walls for personnel entry and emergency escape, with latch-in-place fasteners and airtight gasket seals to maintain plenum pressure integrity when closed.

3mm Chequer PlateWalkable RatingAccess HatchesLatch-Seal Closed
⚙️

FFU Integration — Recirculating Plenum Option

Metrolabs plenums designed for recirculating FFU operation include the structural support grid, power distribution, and alignment receptacles for individual Fan Filter Units (FFU). Each FFU module — comprising an EC fan motor and H14 HEPA filter in a single ceiling-format unit — is individually speed-controlled to allow fine-tuning of air velocity at each ceiling position after installation. FFU speed can be varied across the plenum ceiling to compensate for varying heat loads below (more cooling over equipment, less over empty areas). The plenum structure is engineered to support the dead and live loads of the installed FFU array plus maintenance personnel.

FFU Support GridPower DistributionIndividual VFD SpeedStructural Load Rated
📈

Static Pressure Monitoring — BMS Integration

A digital static pressure transmitter installed in the plenum body measures the plenum internal static pressure continuously — feeding a real-time signal to the BMS. The BMS monitors the plenum pressure against the design setpoint (typically 20–30 Pa above the cleanroom) and triggers an alarm if plenum pressure drops below the threshold — indicating a seal failure, HEPA filter damage, AHU fan trip, or supply duct breach. The plenum pressure signal is also used for AHU VFD control — the AHU fan speed is modulated to maintain constant plenum static pressure as filters progressively load, ensuring constant HEPA face velocity throughout the filter service life without manual re-balancing.

Digital DP Transmitter20–30 Pa SetpointBMS AlarmVFD Auto-Control
Technical Specifications

Metrolabs Air Distribution Plenum — Technical Standards & Performance

Every Metrolabs plenum is designed, fabricated, and commissioned to the following technical parameters:

FeatureMetrolabs SpecificationCleanroom Benefit
Plenum MaterialGI / Aluminium / SS 304Rigid, leak-free, corrosion-resistant structure
Airtight Standard✓ SMACNA ASMACNA Class A leakage testedZero pressure loss — full static pressure to all HEPAs
Internal FinishSmooth, non-porous, covedCleanable — no particle accumulation inside
Insulation25mm NBR / PIR externalNo condensation — no microbial risk in plenum
HEPA InterfaceGel-seal / EPDM housing receptacles100% bypass-free HEPA-to-plenum seal
Static Pressure20–30 Pa above cleanroomUniform HEPA face velocity across entire ceiling
DP MonitoringDigital BMS transmitterConstant HEPA velocity — VFD auto-control
Walkable Top3mm chequer-plate — ratedSafe maintenance access without scaffolding
Full Technical Specification
Casing MaterialGI G-90 / Aluminium / SS 304
Panel Gauge1.0 / 1.2 / 1.5mm (application)
Joint SystemTDF flange + anti-fungal sealant
Leakage StandardSMACNA Class A — site tested
Insulation25mm NBR / PIR closed-cell external
HEPA Receptacle TypeGel-seal (Grade A/B) / EPDM gasket
Design Static Pressure20–30 Pa above cleanroom
HEPA Face Velocity0.36–0.54 m/s (Grade A)
FFU Support LoadStructural rating per project
Top Skin (walkable)3mm chequer-plate GI / Al
Access HatchesLatch-seal — airtight when closed
DP MonitoringDigital transmitter — BMS Modbus
Standards & Compliance
WHO GMPEU Annex 1ISO 14644-4SMACNANABL21 CFR
Plenum vs. Direct-Duct

When to Choose a Plenum Over Direct Ducting

Both plenum and direct-duct configurations are used in cleanroom HVAC. The choice depends on ISO class, number of HEPA positions, energy constraints, and contamination segregation requirements:

Performance Factor Direct Duct Plenum
⚖️ HEPA velocity uniformity
🔴 Imbalanced
✓ Equal at all positions
🌐 Dead zones
✕ Risk if unbalanced
✓ Eliminated
💨 High ACH (200+)
✕ Large AHU needed
✓ FFU recirculation
🌡️ Temperature uniformity
🔴 Hot/cold spots
✓ Mixed, uniform
⚡ Energy efficiency at high ACH
✕ High AHU energy
✓ FFU + small AHU
🚫 Cross-room segregation
✓ Fully segregated
✓ With segmentation
⚙️ Commissioning complexity
High — many balancing pts
✓ Single connection
📋 GMP pharma preference
✓ Grade A–D preferred
✓ With segmentation
The Metrolabs Advantage

Designed for Your Specific Cleanroom — Not Adapted from a Catalogue

Metrolabs does not supply off-the-shelf plenum modules — every plenum is custom-designed from the cleanroom layout drawing, the HEPA grid position plan, and the AHU supply connection details:

📐

Computational Airflow Analysis

Every plenum volume, supply connection size, and supply entry velocity is calculated using HVAC engineering principles to ensure the conversion from duct velocity pressure to static pressure is complete before air reaches the nearest HEPA position. No pressure gradients within the plenum.

🏭

Factory-Fabricated — Minimal Site Debris

Plenum panels are CNC-fabricated and labelled in the factory, arriving on site ready for assembly with pre-formed HEPA housing apertures and pre-fitted housing receptacles — minimising on-site cutting debris that could contaminate the cleanroom below during construction.

SMACNA Pressure Test at Installation

After plenum assembly, the complete plenum is pressure-tested to SMACNA Class A before any HEPA filters are installed — confirming airtight integrity while all joints are still accessible for sealant correction. Test record included in HVAC IQ documentation.

📈

BMS Static Pressure Commissioning

Plenum static pressure measured at commissioning with the AHU at design airflow. DP transmitter calibrated, BMS alarm setpoints programmed, VFD control loop tuned to maintain constant plenum pressure under filter loading. Commissioning data in HVAC IQ record.

💡 Design Insight — Plenum vs. Duct for Pharmaceutical
For GMP pharmaceutical cleanrooms, Metrolabs recommends segmented ducted supply plenums rather than shared recirculating plenums — each room has its own separate plenum segment fed by an individual AHU branch connection, preventing any possibility of air migration between rooms of different GMP grades through the plenum void. Recirculating plenums are recommended for semiconductor, ATMP, and electronics cleanrooms where very high air change rates at ISO Class 3–6 make the energy savings of FFU recirculation economically compelling and cross-room contamination risk is lower. The hybrid approach — recirculating FFU plenum for an ISO 5 inner zone within a ducted ISO 7 outer room — delivers Grade A protection at the product point with Grade C infrastructure investment in the surrounding area.
Applications

Air Distribution Plenums Across Every Regulated Cleanroom Sector

Any cleanroom with more than two terminal HEPA positions benefits from a plenum to ensure uniform velocity distribution:

💊

Pharmaceutical GMP

Segmented ducted plenums for Grade A through D suites — each room a separate plenum with independent AHU branch, VCD, and pressure management. WHO & EU Annex 1 compliant.

🎁

Aseptic & Sterile Filling

Ducted plenum with gel-seal H14 HEPA housings in Grade A laminar flow zones — uniform 0.45 m/s at every ceiling position maintaining Grade A throughout the critical zone.

Electronics & Semiconductor

Recirculating FFU plenums for ISO Class 4–7 — 200–600+ ACH achievable at energy-efficient operating cost through FFU recirculation within the plenum void.

🧮

ATMP & Gene Therapy

Hybrid plenum — FFU ISO 5 inner zone within ducted ISO 7 outer room — delivering Grade A product protection at ATMP manufacturing stations within a Grade C background.

🏥

Hospital OT & Critical Care

Ducted supply plenums for operating theatre and NICU ceiling laminar flow arrays — uniform H13/H14 velocity across the entire surgical zone conforming to HTM 03-01.

🍽️

Food & Beverage

Ducted plenums for FSSAI high-care food production cleanrooms — uniform H13 HEPA supply across the food processing zone with segmentation preventing inter-zone air mixing.

BSL-2 & BSL-3 Labs

Individual sealed ducted plenums per containment zone — no cross-zone air mixing, documented independent pressure management for negative pressure containment room hierarchy.

🔬

NABL & Research Labs

Ducted supply plenums for NABL testing and research cleanrooms — uniform HEPA supply documented in airflow balance record for ISO/IEC 17025 accreditation submission.

The Metrolabs Advantage

Custom-Engineered Plenum Design — From Calculation to Commissioned Performance

Metrolabs designs every plenum from first principles — engineering the plenum volume, supply connection velocity, and static pressure recovery to guarantee uniform HEPA face velocity at every ceiling position before the first cleanroom panel is erected:

📐

HVAC Load Calculation — Plenum Volume & Connection Sizing

Every plenum design begins with an HVAC calculation confirming the AHU supply volume, the supply connection duct velocity, the required plenum cross-section for velocity pressure recovery, and the number and size of HEPA positions. The calculation confirms that the plenum static pressure at the furthest HEPA position exceeds the minimum required to drive the design face velocity through the filter at end-of-life pressure drop.

🏭

CNC Factory Fabrication — Pre-Fitted Housing Apertures

All plenum panels are CNC-cut with HEPA housing apertures to the exact housing dimensions — ensuring a tight, sealant-free fit between the housing and panel that requires only a perimeter bead of anti-fungal sealant for airtight installation. Pre-fitted housing receptacles (gel-seal or gasket) are factory-installed before despatch, eliminating difficult site fitting of precision components in confined ceiling voids.

🔒

Site Pressure Test — Before HEPA Installation

The assembled plenum is pressure-tested to SMACNA Class A before any HEPA filters are loaded — with all housing apertures temporarily sealed with blanking plates. Any leakage is identified and rectified while joints are still accessible. This sequence prevents the scenario where a plenum leakage is only discovered during commissioning when the HEPA filters are already loaded and the ceiling is complete.

📈

Commissioning with Documented Static Pressure Balance

At commissioning, the plenum static pressure is measured at multiple positions across the plenum floor (adjacent to each HEPA housing) using a calibrated micro-manometer — confirming that the static pressure variation between positions is within ±5% of the design value. HEPA face velocity is then measured at each position as the definitive performance check. Balance data is documented in the HVAC OQ record.

Installation & Commissioning

From Ceiling Void to Commissioned Plenum — Four Stages

Metrolabs manages the complete plenum design, fabrication, installation, and commissioning sequence:

01
📐

Design & Volume Calculation

HVAC calculation confirms plenum volume, supply connection size, and static pressure recovery. HEPA positions and housing types specified. Access hatch positions agreed.

02
🏭

Factory Fabrication

CNC panels cut with HEPA apertures. Housing receptacles factory-fitted. Walkable top skin formed. Panels packed, labelled, and dispatched with assembly sequence drawings.

03
🔧

Site Assembly & Pressure Test

Plenum erected and sealed. All joints sealant-applied. Plenum pressure tested to SMACNA Class A with blanking plates in HEPA positions. Leaks corrected. Test record issued.

04

HEPA Load & Commissioning

H14 HEPA filters loaded. Supply airflow set. HEPA face velocity measured at each position. BMS DP alarm configured. Balance data and velocity map in HVAC IQ/OQ.

💡 Design Insight — Avoiding Velocity Imbalance
The most common HVAC commissioning failure in cleanrooms is HEPA velocity imbalance caused by an undersized or improperly positioned AHU supply connection to the plenum. Metrolabs ensures the AHU supply duct enters the plenum at a velocity low enough (typically <3 m/s at the plenum entry) that full static pressure recovery occurs before air reaches the first HEPA position. For large plenums, two supply connections at opposite ends of the plenum — rather than a single central connection — further minimise any residual velocity pressure gradient within the plenum volume.
Regulatory Standards

Air Distribution Plenums Required by Every Major Cleanroom Standard

💊

WHO & EU GMP

WHO GMP and EU Annex 1 require documented evidence that the HVAC system delivers the design air change rate and pressure differential uniformly throughout the classified zone. A plenum with commissioning velocity map data provides exactly this evidence — confirming that every point in the Grade A or B zone receives the design-compliant HEPA supply velocity.

WHO GMP · EU Annex 1
🏭

ISO 14644-4

ISO 14644-4 (cleanroom design) requires that the HVAC air supply system provides a uniform airflow pattern throughout the cleanroom space — specifically preventing high-velocity and stagnant zones. The distribution plenum is the engineering mechanism that satisfies this requirement for multi-HEPA cleanrooms by equalising the supply to every terminal filter position.

ISO 14644-4
📋

ISO 14644-3 HVAC Testing

ISO 14644-3 specifies HVAC performance tests for cleanrooms including airflow velocity uniformity testing at terminal filter positions. The plenum velocity map produced during Metrolabs commissioning constitutes the ISO 14644-3 airflow uniformity test record — demonstrating that HEPA face velocity variation across the ceiling is within the ±20% tolerance specified by the standard.

ISO 14644-3

NABL & 21 CFR Part 11

NABL and US-FDA 21 CFR Part 11 both require that environmental monitoring records include verified HVAC performance data. The BMS static pressure monitoring of the plenum provides the continuous real-time evidence that the supply system is maintaining the design static pressure — and therefore the design HEPA face velocity — throughout the qualification monitoring period.

NABL · 21 CFR Pt11
Design Your Air Distribution Plenum

Ready to Achieve Uniform HEPA Supply Across Every Ceiling Position?

Contact Metrolabs for a free consultation. Our HVAC engineers will assess your cleanroom ceiling grid, HEPA count and positions, AHU supply connection location, and ISO class — then design, fabricate, install, and commission a custom air distribution plenum with SMACNA pressure test and velocity map documentation at handover.

⚖️
Equal Static Pressure — Zero Dead Zones
Every H14 HEPA delivers identical face velocity regardless of position
🔒
SMACNA Class A Airtight — Site Pressure Tested
TDF flanged joints — anti-fungal sealant — test cert in HVAC IQ
💨
Ducted / FFU Recirculating / Hybrid Options
Configured for your ISO class, energy targets, and contamination risk
📈
BMS DP Monitoring — VFD Auto-Control
Constant HEPA velocity through filter life — predictive replacement alert

⚖️ Request a Free Plenum Design Consultation

Consultation Requested!

Our HVAC plenum design team will contact you within 24 working hours.

Immediate: 9840931231