The HVAC system is the most critical structural component of any cleanroom. It is not simply a comfort system — it is the primary engine for contamination control, the mechanism that maintains pressure differentials between GMP grades, and the system that removes particles, heat, and moisture generated by personnel and equipment inside the controlled environment. Metrolabs provides the complete cleanroom HVAC and air handling portfolio — from AHU to terminal HEPA — engineered for long-term ISO class compliance and GMP validation.
Every ISO class is fundamentally defined by the HVAC system performance — not by the wall panels, not by the doors, not by the floor. An ISO Class 7 environment is an ISO Class 7 environment because the HVAC delivers enough HEPA-filtered air changes per hour to dilute and remove particles fast enough to maintain the 352,000 particles/m³ at 0.5μm limit. If the HVAC fails, the ISO class is lost within minutes.
Cleanroom HVAC controls particle concentration by constantly supplying clean, filtered air at a rate that dilutes and displaces particles generated by personnel, equipment, and processes faster than they can accumulate. For ISO Class 5 (Grade A), 240–360 air changes per hour are required. For ISO Class 8, 20–60 ACH. The AHU and distribution system must maintain this rate continuously.
Pharmaceutical cleanrooms operate on a positive pressure cascade — Grade A at highest pressure, flowing down through B, C, D to corridor. The HVAC system maintains the design differential (typically 10–15 Pa per step) through precisely balanced supply and return airflows. Pressure sensors monitor the differential continuously and the AHU VFD adjusts fan speed in real time to compensate for door openings and infiltration.
Most pharmaceutical and biotech processes specify temperature at 20–22°C ±2°C and relative humidity at 45–55% ±5% RH. Tight T&H control prevents static electricity buildup (humidity too low), microbial growth (humidity too high), and product stability risks (temperature excursions). The AHU cooling coil, reheating coil, and humidifier/dehumidifier work together under PLC control to maintain these setpoints.
All HVAC parameters — pressure differentials, temperature, humidity, HEPA filter differential pressure, fan speeds, alarm status — are monitored and logged by the Building Management System (BMS). The data log is the primary environmental monitoring record for GMP and ISO validation — demonstrating that the cleanroom consistently maintained its specified conditions during production.
Metrolabs supplies the complete cleanroom HVAC system from a single source — every component from the AHU intake to the terminal HEPA housing engineered for the same ISO class and GMP compliance standard:
The primary engine of the cleanroom HVAC system. Metrolabs AHUs are constructed with 50mm double-skin insulated casing (thermal and acoustic) with an SS 304 aseptic interior skin featuring sloped drain pan and R20 coved corners — preventing standing water and microbial growth. Equipped with high-static plug fans with Variable Frequency Drives (VFDs) to maintain constant airflow as filters progressively load. Cooling coil, reheating coil, humidifier, and dehumidifier section all factory-assembled and tested.
The air delivery network of the cleanroom. Galvanised Iron (GI) ducting is the standard for pharmaceutical HVAC — internally smooth bore to minimise friction and particle accumulation, externally insulated to prevent condensation. Every joint is sealed with high-grade compressed foam gaskets to eliminate air leakage that would undermine the pressure gradient. Ducting is pressure-tested after installation to verify leak-free integrity to SMACNA Class A standards. Aluminium and SS ducting available for aggressive chemical environments and VHP sterilization compatibility.
The first and second stages of the three-tier filtration system. G4 pre-filters (90% efficiency for synthetic dust, EN 779) capture large particles to protect cooling coils and extend the life of downstream fine and HEPA filters. F7 fine filters (80% efficiency at MPPS) and F9 fine filters (95% efficiency at MPPS) then capture sub-micron particles, forming a secondary barrier before the terminal HEPA stage. Filter differential pressure gauges on each stage trigger alerts when replacement is due.
The final and most critical barrier against contamination — ceiling-mounted H13 (99.97% at 0.3μm) or H14 (99.995% at 0.3μm) HEPA filters in purpose-designed terminal housings. Installed at the point of air entry into the clean zone, ensuring only ultra-pure air enters the sterile environment. Every HEPA filter is factory-validated by PAO (Polyalphaolefin) or DOP testing and supplied with a test certificate. Terminal housings include integral test ports for in-situ integrity testing without disturbing the room structure.
A pressurised equalising chamber above the cleanroom ceiling that receives conditioned air from the AHU ducting and distributes it uniformly to multiple HEPA housings or diffusers across the ceiling grid. The plenum eliminates velocity imbalances between HEPA filter positions — ensuring every terminal filter receives the same static pressure and delivers the same airflow velocity to the clean zone below. Without a properly designed plenum, some HEPA units will be starved of airflow while others are over-pressurised, creating dead zones and turbulent areas within the cleanroom.
The final air delivery devices that introduce conditioned air into the cleanroom environment. Perforated ceiling diffusers in Grade A / ISO Class 5 zones deliver laminar (unidirectional) airflow at 0.36–0.54 m/s to create a “piston effect” — pushing air and particles in a single direction, away from the critical work zone. Swirl diffusers in Grade C/D zones (turbulent flow) promote rapid dilution and mixing of incoming clean air with room air to achieve rapid contamination reduction. All grilles and diffusers are flush-mounted and removable for filter cleaning without tools.
Low-level return air extracts used to remove contaminated room air from near the floor — the critical “clean sweep” principle of pharmaceutical cleanroom design. By extracting return air at floor level (rather than at ceiling level), the HVAC system pulls particles downward and away from the work surface and personnel breathing zone. Return Air Risers are integrated into the cleanroom wall panel system with flush-mounted perforated covers that can be removed for cleaning, aligned precisely with the modular panel grid.
Electronic differential pressure sensors measure the pressure difference between adjacent cleanroom zones (e.g., Grade B at 15 Pa vs Grade C at 10 Pa) in real time. Digital magnehelic gauges provide local readings on both sides of every door; electronic transmitters feed the BMS with continuous data. Alarm logic triggers visual and audible alerts when the differential falls below the specified minimum — indicating a door left open, a fan fault, or a ductwork breach requiring immediate investigation. Integrated with the AHU VFD to auto-correct fan speed when pressure deviates from setpoint.
PLC-based T&H control systems maintain temperature within ±0.5°C and relative humidity within ±2% RH of setpoint — continuously and automatically. The PLC manages the AHU cooling coil (chilled water or DX), reheating coil, humidifier (steam or ultrasonic), and dehumidifier in coordinated sequence to maintain target conditions. All T&H data is automatically logged with timestamped, 21 CFR Part 11-compliant records for GMP and ISO 14644-2 environmental monitoring reports — eliminating manual temperature logging and the compliance risk it creates.
A single HEPA filter at the point of use is insufficient — it will load rapidly with particles that pre-filters would have captured, requiring expensive frequent replacement and risking filter integrity failure. Metrolabs designs a tiered filtration strategy that progressively removes particles at each stage:
The first line of defence — installed in the AHU intake, the G4 panel filter captures 90% of synthetic dust (particles >10μm) including lint, pollen, and coarse atmospheric particles. Primary purpose: protect the cooling coil from fouling (which would reduce heat transfer efficiency) and extend the service life of the downstream fine and HEPA filters by removing the bulk of the particle load.
G4 — >90% Synthetic Dust Efficiency (EN 779)Installed downstream of the cooling coil, the F7 bag filter captures 80–90% of particles at the Most Penetrating Particle Size (MPPS — 0.3μm). Acts as the primary protection for the terminal HEPA filters, reducing the particle burden reaching the H13/H14 stage by up to 90% — dramatically extending HEPA service life from 1–2 years to 5–8 years in typical pharmaceutical environments.
F7 — 80–90% at MPPS (EN 779)Used in ISO Class 3–6 systems requiring maximum protection of the terminal HEPA filters, the F9 bag filter captures 95% of particles at MPPS. For Grade A and B pharmaceutical facilities, the combination of F9 pre-filtration and H14 terminal filtration provides multi-layer contamination control that ensures HEPA integrity is maintained over extended validation periods.
F9 — 95% at MPPS (EN 779)Ceiling-mounted terminal HEPA filter rated H13 (EN 1822) — capturing 99.97% of particles at 0.3μm. Used for ISO Class 6–7 pharmaceutical cleanrooms (Grade C), hospital operating theatres, and food manufacturing clean zones. PAO/DOP factory-tested and certified. In-situ test port for periodic re-validation without room disruption.
H13 — 99.97% @ 0.3μm (EN 1822)The highest-specification terminal filter for ISO Class 3–5 environments (Grade A/B) — H14 (EN 1822) captures 99.995% of particles at 0.3μm. Mandatory for aseptic pharmaceutical manufacturing, injectable fill-finish, ATMP production, and BSL-3 containment zones. Each unit factory PAO/DOP tested; in-situ test port allows re-validation at defined intervals without disturbing the ceiling grid or room environment.
H14 — 99.995% @ 0.3μm (EN 1822)The HVAC system maintains a continuously decreasing pressure cascade from the highest-grade clean zone outward. Air always flows from higher to lower pressure — preventing lower-grade or uncontrolled air from flowing into higher-grade zones:
Accurate, validated, documented environmental control is the difference between a cleanroom that passes inspection and one that fails. Metrolabs PLC-based control systems provide real-time accuracy and automatic audit-trail logging:
PLC manages the AHU cooling coil (chilled water) and electric reheating section in coordinated sequence to maintain room temperature within ±0.5°C of setpoint — exceeding ISO 14644 and WHO GMP requirements. Cascade control strategy anticipates HVAC lag to prevent overshoot and undershoot transients.
Steam injection humidifier (or ultrasonic for cold processes) and chilled coil dehumidification maintain relative humidity within ±2% RH. Critical for pharmaceutical powder handling (static electricity prevention), cell culture stability, and electronics cleanrooms.
All HVAC parameters — pressure, temperature, humidity, fan speed, filter differential pressure, alarm status — fed to the Building Management System via Modbus, BACnet, or direct IO. Dashboard display in facility control room with historical trend logging for ISO 14644-2 periodic review.
Automatic, tamper-evident, timestamp-verified electronic logs of all environmental parameters — meeting US-FDA 21 CFR Part 11 requirements. Logs are accessible for GMP audit, ISO validation review, and regulatory submission in CSV, PDF, or system-native format. Manual paper temperature logs are eliminated.
Each component in the Metrolabs HVAC system has a dedicated specification page — click to explore detailed technical content, specifications, and application guidance:
Every component in the Metrolabs cleanroom HVAC system, its primary function, and its material or performance standard:
| Component | Primary Function | Key Standard / Rating | Compliance |
|---|---|---|---|
| Air Handling Unit (AHU) | Filter, condition, and circulate air to cleanroom | SS 304 interior, VFD fan, 50mm double-skin | WHO GMP |
| GI Ducting | Air transport from AHU to ceiling plenum | SMACNA Class A — <1% leakage | SMACNA |
| G4 Pre-Filter | Coarse particle removal — protect coils & HEPA | EN 779 — >90% synthetic dust | EN 779 |
| F7 / F9 Fine Filter | Sub-micron pre-filtration — protect terminal HEPA | EN 779 — 80–95% at MPPS | EN 779 |
| H13 / H14 HEPA | Terminal filtration — ultra-pure air delivery | EN 1822 — 99.97% / 99.995% @ 0.3μm | EN 1822 |
| Distribution Plenum | Equalise pressure to all HEPA terminal positions | Uniform velocity — no dead zones | ISO 14644 |
| Air Grilles / Diffusers | Laminar or turbulent air delivery into cleanroom | 0.36–0.54 m/s (Grade A laminar) | ISO 14644 |
| Return Air Risers | Low-level extract — particle sweep to AHU return | Floor-level flush panel integration | GMP Design |
| Differential Pressure Sensors | Monitor & alarm pressure cascade integrity | Digital / Magnehelic — BMS alarm | ISO 14644-2 |
| T&H Controllers (PLC) | Maintain temperature & humidity within setpoints | ±0.5°C / ±2% RH — 21 CFR Pt 11 log | 21 CFR Pt11 |
Every cleanroom ISO class requires HVAC — from the simplest ISO 8 food processing area to the most demanding ISO 3 semiconductor fab:
Grade A through D HVAC systems — H14 HEPA laminar flow for aseptic, H13 for C/D grades, with full GMP pressure cascade and validated T&H control.
ISO Class 5 laminar downflow HVAC at 0.45 m/s for Grade A workstations and filling lines — 99.995% H14 HEPA with PAO integrity testing.
Positive pressure HVAC for operating theatres (ISO 5), negative pressure for isolation rooms, and cascade control for hospital cleanroom areas.
FSSAI and HACCP-compliant HVAC for high-care food production — H13 HEPA filtration, positive pressure, and humidity control to prevent microbial growth.
ISO Class 4–7 HVAC with laminar or mixed-flow air delivery for wafer fab, PCB assembly, and precision electronics — tight humidity control for ESD prevention.
HVAC for cell therapy, mRNA, and gene therapy GMP suites — Grade A/B cascade, VHP-compatible AHU interior, and 21 CFR Part 11 environmental logging.
Negative pressure HVAC for biosafety containment — maintaining inward airflow at all times, with HEPA-filtered exhaust and differential pressure alarm monitoring.
HVAC for NABL-accredited testing and research cleanrooms — controlled ISO class environment with documented temperature, humidity, and particle monitoring.
Metrolabs HVAC systems are designed, supplied, installed, and commissioned as an integrated system — not as disconnected components from different suppliers with interface gaps between them:
AHU, ducting, filters, plenums, grilles, risers, sensors, and control systems — all specified, supplied, installed, and tested under a single Metrolabs contract. No interface gaps between equipment suppliers. One project manager, one performance guarantee.
All Metrolabs HVAC systems are designed for full BMS integration (Modbus, BACnet, dry contact) and tested to withstand room-wide VHP (Vaporized Hydrogen Peroxide) sterilisation cycles — including AHU casing, coils, and internal components.
21 CFR Part 11-compliant T&H and pressure data logging from Day 1 of operation. Supports ISO 14644-2 periodic review data requirements and WHO/EU GMP environmental monitoring validation protocols without additional third-party monitoring equipment.
Installation Qualification (IQ) and Operational Qualification (OQ) documentation package at handover — including HEPA PAO/DOP test certificates, ductwork pressure test records, VFD commissioning data, T&H calibration certificates, and BMS configuration as-built drawings.
Each component in the Metrolabs cleanroom HVAC portfolio has a dedicated product page with full specifications, application guidance, and compliance data:
WHO GMP and EU Annex 1 specify minimum air change rates, pressure differentials, HEPA filtration requirements, and T&H control accuracy for each GMP grade. The HVAC system and its qualification records are the primary evidence of GMP compliance inspected by WHO, EU, and national pharma regulators.
WHO GMP · EU Annex 1ISO 14644-1 defines cleanroom classification by particle count — achieved by HVAC air changes and HEPA filtration. ISO 14644-2 specifies the monitoring frequency, parameters, and data logging requirements for ongoing cleanroom performance verification — satisfied by the Metrolabs BMS and T&H logging system.
ISO 14644-1 · -2FDA 21 CFR Part 11 requires that electronic records generated by facility environmental monitoring systems (temperature, pressure, humidity data) meet electronic record authenticity and integrity requirements. Metrolabs T&H controller logs satisfy these requirements directly.
21 CFR Part 11NABL laboratory accreditation requires documented evidence of controlled environmental conditions in test areas — temperature, humidity, and particle counts within specified limits. Metrolabs HVAC with BMS data logging provides this continuous documented evidence for NABL assessment submissions.
NABL · ISO 17025Contact Metrolabs for a free HVAC consultation. Our engineers will assess your ISO class requirements, GMP grade, facility layout, and compliance obligations — then design, supply, install, and commission a complete cleanroom HVAC system from AHU to terminal HEPA, with full IQ/OQ documentation at handover.
Our cleanroom HVAC team will contact you within 24 working hours.
Immediate: 9840931231