Cleanroom Temperature & Humidity Controllers – PID Climate Control for ISO & GMP | Metrolabs Chennai
📍 Chennai, Tamil Nadu | Pan India 📞 9840931231 ✉ metrolabs1@gmail.com
Home Cleanroom Home HVAC & Air Handling T&H Controllers
±0.3°C / ±2% RH · PID · Modbus / BACnet · 21 CFR Part 11

Cleanroom Temperature & Humidity Controllers — Climate Stability for Sensitive Research

Temperature and humidity are the two environmental parameters most directly responsible for product stability, microbial growth, static electricity, and personnel safety in a cleanroom. A ±2°C temperature excursion in a biological manufacturing suite can invalidate a production batch. A 10% RH spike in a powder handling area can cause clumping, flowability failure, and microbial contamination. Metrolabs T&H Controllers are the central nervous system of your AHU — PID-controlled precision instruments that maintain temperature to ±0.3°C and relative humidity to ±2% RH, continuously, automatically, and with 21 CFR Part 11-compliant electronic data logging.

±0.3°C Accuracy ±2% RH Control PID Logic Modbus / BACnet Capacitive / PT100 21 CFR Part 11
T&H Controller Quick-Reference
Temperature Accuracy±0.3°C of setpoint
Humidity Accuracy±2.0% RH of setpoint
Control AlgorithmPID (Proportional-Integral-Derivative)
Temp SensorPT100 / PT1000 RTD
Humidity SensorCapacitive polymer element
CommunicationModbus RTU / BACnet / 4–20mA
🌡️
±0.3°C
Temp Accuracy
💧
±2%RH
RH Accuracy
📍
Pan-India
Install
🌡️
±0.3°C Temperature — PID Precision Control
💧
±2% RH Humidity — No Hunting or Overshoot
⚙️
Dual-Channel PID — Temp + RH Coordinated
📈
Modbus / BACnet / 4–20mA — BMS Ready
📋
21 CFR Part 11 — Audit-Ready Data Logging
VHP Compatible — Flush Panel Mount
T&H PID Control Loop — AHU Component Coordination
PLC CONTROLLER PID Algorithm T setpoint: 20°C ±0.3 RH setpoint: 50% ±2 SENSORS PT100/PT1000 (Temp) Capacitive (RH) Measured values BMS / DATA LOGGER 21 CFR Pt 11 · Modbus · BACnet T&H log COOLING COIL Chilled water valve REHEATING COIL LTHW / electric HUMIDIFIER Steam / ultrasonic DEHUMIDIFIER Cooling coil condensate PID control signals CLEAN ROOM 20°C ±0.3 50% RH ±2 ALARM OUTPUTS Visual LED · Audible · BMS notify Dead-band configurable per zone PLC coordinates all 4 AHU outputs in cascade — no hunting, minimal energy
⚙️ PID Cascade Control
PLC coordinates cooling, reheating, humidification, and dehumidification in one algorithm — no hunting.
📈 BMS Data Logging
All T&H readings timestamped to BMS via Modbus/BACnet — 21 CFR Part 11 records from Day 1.
🔋
PT100 + Capacitive Sensors
Low-drift PT100/PT1000 for temperature. Capacitive polymer for humidity — long-term stable.
⚠️ Alarm Dead-Band
Configurable dead-band prevents nuisance alarms during normal process transients.
Why T&H Control Is Non-Negotiable

Climate Is Not a Comfort Parameter — It Is a Process Critical Variable

In pharmaceutical and research cleanrooms, temperature and humidity are not set for personnel comfort — they are set because the product or process specification requires them. Deviating outside the specified range is a GMP deviation that requires investigation, batch disposition review, and potentially product rejection.

🌡️

Temperature — Product Stability and Assay Validity

Biological products — monoclonal antibodies, vaccines, cell therapy products, blood products — are temperature-sensitive to a degree that a ±2°C temperature excursion above specification can reduce potency, cause precipitation, or invalidate a stability study. Even in non-biological pharmaceutical manufacturing, temperature control at ±0.3°C ensures that viscosity, crystallisation, and chemical reaction rates in API synthesis remain within validated process parameters. The PLC-PID controller maintains the supply air temperature at setpoint with no overshoot — the pharmaceutical process sees the room temperature it was validated at, not a cycling approximation.

💧

Relative Humidity — Microbial Risk and Product Integrity

Relative humidity above 60% creates conditions that support microbial growth on surfaces, packaging materials, and product — a critical contamination risk in pharmaceutical and food cleanrooms. Below 40% RH, static electricity builds up rapidly, creating product loss in powder handling and electronic component damage in electronics cleanrooms. The pharmaceutical GMP specification (typically 45–55% RH) is set precisely within the window that minimises both microbial risk and static risk — the T&H controller must maintain the room within this narrow band continuously and automatically.

⚙️

PID Algorithm — Eliminating Hunting and Energy Waste

Standard on/off controllers — or simple proportional controllers without integral and derivative terms — cause the cleanroom temperature and humidity to oscillate continuously around the setpoint — a phenomenon called “hunting.” Every overshoot cycles the compressor and heater, accelerating wear and consuming more energy. The PID algorithm uses the error (P), the accumulated error over time (I), and the rate of change of error (D) together to calculate a smooth, precisely calibrated output that drives the system to setpoint and holds it there without oscillation. The derivative term in particular prevents overshoot — anticipating the approach to setpoint and reducing output before the setpoint is reached.

📋

GMP Compliance — Continuous Documented Environmental Data

WHO GMP, EU Annex 1, and US-FDA 21 CFR Part 11 require continuous monitoring of temperature and humidity in all classified cleanroom zones, with documented alarm limits, timestamped data records, and SOP response to excursions. The Metrolabs T&H controller BMS data feed provides this compliance evidence automatically — eliminating manual paper temperature logs that are incomplete, falsifiable, and inadmissible as GMP evidence.

Controller & Sensor Types

Six T&H Controller & Sensor Configurations

Metrolabs supplies T&H monitoring and control systems in six configurations — from standalone room indicators to fully integrated multi-zone PLC systems:

🌡️

Wall-Flush Room T&H Display — Personnel Status

A flush-mounted wall display unit showing live temperature and relative humidity with large, high-visibility digital readout visible from across the room. The display housing sits flush with the modular panel surface — zero protrusion, smooth VHP-resistant glass or membrane front face, zero-ledge installation. The display shows current T and RH values alongside the setpoint — allowing personnel to verify conditions immediately on entering the zone, a key part of the entry SOP. Integrated alarm LEDs (green = within setpoint, red = outside dead-band) provide instant visual status without requiring personnel to read the numeric value. The display unit includes an internal PT100 sensor element and capacitive RH element — positioned within the unit housing to measure representative room air temperature and humidity, not wall surface temperature.

Flush MountGlass/Membrane FaceGreen/Red LEDVHP Resistant
⚙️

PLC-Based AHU T&H Controller — Dual-Channel PID

The core control system for the cleanroom AHU — a PLC (Programmable Logic Controller) with HMI touchscreen, running dual-channel PID algorithms for simultaneous, coordinated temperature and humidity control. Channel 1 controls the cooling coil chilled water valve and the reheating coil output to achieve the supply air temperature setpoint. Channel 2 controls the humidifier output and the dehumidifier (via cooling coil temperature setpoint modulation) to achieve the supply air humidity setpoint. The two channels interact in a coordinated cascade — the controller knows that increasing humidity through the humidifier will also raise the supply air temperature, and pre-compensates the reheating coil accordingly — preventing the hunting and overshoot that plague dual-channel on/off control systems. The PLC connects to the BMS via Modbus RTU, BACnet, or 4–20mA outputs.

Dual PID ChannelsCoordinated CascadeHMI TouchscreenModbus / BACnet
📈

PT100 / PT1000 RTD Temperature Sensor

Platinum Resistance Temperature Detectors (RTDs) are the industry standard for pharmaceutical cleanroom temperature measurement — providing better accuracy, stability, and linearity than thermistors or thermocouples over the 15–25°C cleanroom temperature range. The PT100 (100Ω at 0°C) and PT1000 (1000Ω at 0°C) sensors follow a precise, internationally standardised resistance-temperature relationship (IEC 60751) that allows high-accuracy measurement without individual calibration of each sensor — any compliant PT100 reads the same temperature for the same resistance. Low drift over extended periods means recalibration intervals are long. Metrolabs uses 4-wire PT100 connection to eliminate lead resistance errors in long cable runs — critical for sensor elements installed in the AHU air stream at distances from the controller panel.

IEC 607514-Wire ConnectionLow Long-Term DriftAHU / Room Mount
💧

Capacitive Polymer Humidity Sensor

The standard RH sensor for pharmaceutical cleanroom applications — a thin-film capacitive polymer element whose capacitance changes proportionally with relative humidity. Capacitive sensors provide excellent linearity across the 20–80% RH range (the pharmaceutical cleanroom operating range), fast response time, and stable performance over extended operation without the drift and hysteresis that characterise resistive humidity sensors. The polymer element is protected by a stainless steel sintered metal filter cover — preventing dust and particulate contamination from reaching the sensing surface while allowing full gas-phase humidity measurement. Metrolabs specifies NIST-traceable calibrated humidity sensors — supplied with a calibration certificate showing the measured accuracy at three reference humidity points across the measurement range.

Capacitive PolymerSS Sintered FilterNIST Traceable CalFast Response
🌐

Multi-Zone Centralised T&H Management System

For pharmaceutical suites, hospital complexes, and research facilities with multiple independently controlled cleanroom zones, Metrolabs designs a centralised T&H management system — a single PLC/SCADA hub monitoring and controlling T&H in all zones simultaneously. Each zone has its own room-mounted sensors feeding the central PLC, which runs independent PID loops for each zone’s AHU. The central HMI displays all zone T&H values on a single mimic diagram — facility managers can see the environmental status of every room from one location. Zone-specific alarm setpoints, dead-bands, and logging intervals are independently configurable. All zone data is logged to a central data logger for unified GMP environmental monitoring records. Supports up to 64 zones on a single Modbus network.

Up to 64 ZonesCentral HMI MimicIndependent PID / ZoneUnified GMP Log
🔩

Standalone Validated Data Logger — 21 CFR Part 11

For facilities requiring environmental monitoring evidence independent of the AHU control system — providing a second, redundant data trail that cannot be affected by AHU control system faults — Metrolabs supplies standalone validated data loggers with their own independent T&H sensor elements, local storage of timestamped records, and USB/Ethernet export to validated data management software. The standalone logger satisfies the 21 CFR Part 11 requirement for audit trail integrity — all records are electronically signed, tamper-evident, and access-controlled by user role. The logger continues recording even when BMS communication is lost — ensuring continuous environmental monitoring data during system maintenance or communication failures. Calibration certificates for all sensor elements supplied. Recommended for all pharmaceutical GMP facilities with US-FDA or PMDA submission requirements.

Independent Redundant21 CFR Part 11USB / Ethernet ExportOffline Capable
Technical Specifications

Metrolabs T&H Controller — Technical Standards & Accuracy

Every Metrolabs T&H controller system is commissioned and documented to the following performance parameters:

FeatureMetrolabs StandardBenefit
Temperature Accuracy±0.3°C of setpointPrecise enough for biological & chemical process validation
Humidity Accuracy✓ GMP Spec±2.0% RH of setpointWithin pharmaceutical 45–55% RH specification range
Control AlgorithmPID (P + I + D terms)No hunting, no overshoot — energy efficient
Temperature SensorPT100 / PT1000 RTD (IEC 60751)Long-term stable — minimal recalibration
Humidity SensorCapacitive polymer elementAccurate 20–80% RH — fast response
CommunicationModbus RTU / BACnet / 4–20mAIntegrates with any BMS platform
DisplayFlush-mounted digital HMIZero-ledge — VHP resistant — GMP hygienic
Data Logging21 CFR Part 11 compliantAudit-ready — tamper-evident — WHO/FDA accepted
Full Technical Specification
Temperature Range0–50°C (room / AHU)
Temperature Accuracy±0.3°C of setpoint
Humidity Range10–90% RH
Humidity Accuracy±2.0% RH of setpoint
Control AlgorithmPID — auto-tunable
Temp Sensor TypePT100 / PT1000 (4-wire)
RH Sensor TypeCapacitive polymer — sintered SS
Output Channels2 (temp + RH) — coordinated
Analog Output4–20mA (2 channels)
Digital ProtocolModbus RTU / BACnet MSTP / IP
Data Logging21 CFR Part 11 — timestamp — access control
DisplayFlush-mount — VHP resistant
Standards & Compliance
WHO GMPEU Annex 1ISO 14644-221 CFR Pt11NABLIEC 60751
Sensor Placement & Data Management

Placing Sensors in Representative Zones — Data That Reflects Reality

A T&H sensor installed in the wrong location produces data that misrepresents the actual cleanroom conditions — potentially masking excursions in the critical work zone while showing compliant values at the sensor position. Metrolabs follows ISO 14644-2 sensor positioning principles:

📍

Representative Zone Placement — Away from Disturbances

Sensors are positioned in the representative zone of the cleanroom — the area most affected by the process and most representative of the conditions to which the product or personnel is exposed. This means away from door draughts (which create localised cool or warm air pockets), away from heat-generating equipment (centrifuges, incubators, process vessels), and away from HEPA supply diffusers (which create locally cool, low-humidity microclimates directly below the filter). Typically 1.2–1.5m above floor level, in the room quadrant opposite the primary HEPA supply.

1.2–1.5m heightAway from HEPAISO 14644-2
🔄

AHU Supply Air Sensor — Control Reference

A dedicated supply air T&H sensor is installed in the AHU supply duct downstream of the reheating coil and humidifier — this is the sensor the PID controller uses as its control feedback. The supply air setpoint is typically calibrated so that the room sensor (at representative zone) reads the specified room conditions — the supply air temperature and humidity are slightly different from the room values due to mixing with return air in the plenum.

AHU ductPID feedbackSupply air T&H
📋

Audit-Ready Data Logging — Batch Environmental Records

Every T&H reading is timestamped and stored in the BMS data logger with the sensor ID, room ID, value, alarm status (normal / warning / alarm), and operator acknowledgement for any alarm event. The data record supports a complete batch environmental monitoring review — demonstrating that temperature and humidity remained within the validated range throughout the production batch from start to finish. Data is exportable in CSV and PDF format with an electronic audit trail of all access and modifications.

Batch recordsAlarm historyCSV / PDF export

Alarm Dead-Band — Preventing Nuisance Alarms

A configurable dead-band (typically ±0.5°C for temperature, ±3% for RH beyond the control setpoint) prevents alarms from triggering during normal transient fluctuations — door openings, occupancy changes, process heat load variations — while still alarming promptly on genuine out-of-specification excursions that require investigation and documentation. The dead-band is set wider than the control accuracy specification to prevent the alarm from triggering every time the PID makes a minor control correction.

Configurable±0.5°C / ±3%RH typicalGMP alarm limit
Live T&H Room Status — BMS Display
🌡️
20.2
°C
Temperature
✓ Normal
💧
51.8
% RH
Humidity
✓ Normal
Logged Data — Last 6 Hours (Room 3 — Grade B)
14:0020.1°C · 51.2% RH
13:0020.3°C · 52.4% RH
12:0020.0°C · 58.1% RH⚠ RH warn
11:0020.4°C · 51.8% RH
10:0020.2°C · 50.9% RH
09:0019.9°C · 49.5% RH
08:0020.1°C · 51.0% RH
The 12:00 RH warning (58.1%) was auto-corrected by the PLC increasing dehumidifier output. Duration: 4 minutes. Alarm was acknowledged by QA Supervisor (ID: QA-04) and logged with the note “Gowning room door held open — transient event.” No SOP deviation raised.
Applications

T&H Controllers Across Every Regulated Cleanroom Sector

💊

Pharmaceutical GMP

PLC-PID dual-channel control for Grade A through D AHUs — ±0.3°C and ±2% RH with 21 CFR Part 11 logging for WHO, US-FDA, and EU regulatory batch records.

🎁

Aseptic & Biologicals

High-accuracy T&H control for Grade A/B aseptic manufacturing — temperature stability critical for biological product potency and sterility assurance throughout filling.

🧪

Biotech & Cell Culture

Multi-zone centralised T&H management for cell therapy and ATMP GMP suites — each culture room independently controlled with unified batch environmental records.

🏥

Hospital & Healthcare

T&H control for hospital cleanrooms, OTs, and CSSD — temperature and humidity within NHS/NABH standards, integrated with hospital BMS for centralised monitoring.

Electronics Cleanrooms

Humidity control at 45–55% RH for semiconductor and electronics cleanrooms — preventing ESD events and ensuring stable process yields in humidity-sensitive manufacturing.

🍽️

Food & Beverage

T&H control for FSSAI high-care food cleanrooms — humidity maintained below 60% RH to prevent microbial growth on food contact surfaces and packaging.

🔬

NABL Research Labs

Standalone validated data loggers for NABL-accredited testing labs — NIST-traceable sensor calibration and 21 CFR Part 11 records for ISO/IEC 17025 submissions.

🏘️

Long-Term Storage & Stability

T&H monitoring and control for pharmaceutical stability chambers and product storage rooms — continuous logged evidence of storage conditions for stability study data.

The Metrolabs Advantage

Fully Integrated Environmental Strategy — Not Just a Thermostat

Metrolabs does not supply standalone thermostats — we design and commission a complete, validated environmental monitoring and control system, custom-programmed to the specific AHU, zone layout, and regulatory requirements of each project:

⚙️

Custom-Programmed PID Tuning per AHU

Every AHU has a different thermal mass, cooling coil capacity, humidifier output, and duct length — meaning the PID parameters (gain, integral time, derivative time) that produce stable, hunting-free control are different for every installation. Metrolabs commissions the PID parameters through step-response testing at first commissioning, producing the optimal settings for each specific AHU rather than factory defaults that may produce hunting in that specific system.

🔄

Coordinated Dual-Channel — Temperature and Humidity in Balance

The most common T&H control failure is running temperature and humidity as two completely independent control loops — when the humidifier adds moisture to increase RH, the supply air temperature rises, causing the heating controller to reduce output, which then drops the RH back as the air cools. Metrolabs programmes the dual PID channels to run in coordinated cascade — the temperature controller knows about humidifier output changes and pre-compensates the reheating coil, eliminating the interaction-induced hunting entirely.

📋

Audit-Ready from Day 1 — 21 CFR Part 11

The BMS T&H data logging is configured, access-controlled, and validated at commissioning — the GMP environmental monitoring record is active from the first day of cleanroom operation. Each log entry is electronically signed, timestamped, and stored in a tamper-evident format. Alarm event records include operator acknowledgement ID. The system is pre-configured to export the standard environmental monitoring report format required for batch record submission.

🔧

VHP-Compatible — No Damage After 500+ Cycles

All sensor housings, display faces, and controller front panels are specified for full VHP exposure — the materials are tested to maintain dimensional stability, sealing performance, and electrical function after 500+ VHP sterilisation cycles at up to 1000 ppm H O concentration. This prevents the material degradation, condensation of VHP residue on sensor elements, and seal failures that cause T&H controller malfunctions in facilities with regular room-wide VHP programmes.

💡 Technical Insight — Sensor Placement Away from Heat Sources
To ensure the most reliable, regulatory-accepted T&H data, Metrolabs engineers place sensors in “representative zones” — positions that reflect the actual environmental conditions experienced by the product or process, rather than positions near door draughts, HEPA supply diffusers, or heat-generating equipment. A sensor placed 600mm from a HEPA diffuser will read 2–3°C lower than the room average — appearing compliant while the rest of the room may be out of specification. Correct sensor positioning is as important as sensor accuracy — Metrolabs engineers confirm representative zone positions during cleanroom design, ensuring that the T&H data record is defensible during regulatory inspection.

T&H Controller Type Comparison

Capability On/Off PLC-PID
± Temperature control
±1.5–2°C
±0.3°C
± RH control
±5–8% RH
±2% RH
⚙️ Hunting / overshoot
✕ Constant hunting
✓ Eliminated
🔄 Dual-channel coordination
✕ Independent
✓ Coordinated cascade
📈 BMS integration
🔴 Limited
✓ Modbus / BACnet
📋 21 CFR Pt11 logging
✕ Paper only
✓ Electronic auto-log
⚡ Energy efficiency
✕ High cycling
✓ Smooth modulation
Installation & Commissioning

From Controller Selection to Validated PID Tuning & 21 CFR Logging

Metrolabs manages the complete T&H controller installation from sensor placement through PID tuning, BMS integration, and validated data logging confirmation:

01
📐

Sensor Position Design

Representative zone positions confirmed per ISO 14644-2. AHU supply duct sensor position agreed for PID feedback. Room display unit positions confirmed for zone entry SOP compliance. Cable route plan produced.

02
⚙️

Controller Installation & Wiring

PLC, sensors, and displays flush-installed. PT100 4-wire connections made to eliminate lead resistance errors. 4–20mA or Modbus cable run to BMS. All connections tested for signal integrity before PLC power-on.

03
📈

PID Tuning & BMS Integration

Step-response test on AHU: temperature step change applied, controller response recorded. PID parameters (Kp, Ti, Td) calculated and programmed. BMS trend logging confirmed active. Alarm setpoints, dead-bands, and delay timers configured per zone.

04

Calibration Verification & IQ Issue

Sensor output verified against NIST-traceable reference at three temperature and RH points. PID stability confirmed by 24-hour trend run. Alarm response test performed and logged. All calibration certs and tuning records in HVAC IQ documentation.

Regulatory Standards

T&H Monitoring Required by Every Major Cleanroom Regulatory Framework

💊

WHO & EU GMP

WHO GMP and EU Annex 1 require continuous monitoring of temperature and humidity with defined alarm limits and documented SOP response to excursions. The PLC T&H controller BMS log provides the primary environmental monitoring evidence for GMP batch record review and regulatory inspection.

WHO GMP · EU Annex 1
🏭

ISO 14644-2

ISO 14644-2 specifies temperature and humidity as primary cleanroom monitoring parameters with defined monitoring intervals, alarm limits, and data review frequency. Metrolabs T&H controller BMS logging satisfies the continuous monitoring requirement directly — data reviewed at defined intervals as part of the ISO 14644-2 periodic review programme.

ISO 14644-2
📋

21 CFR Part 11

US-FDA 21 CFR Part 11 requires that electronic environmental monitoring records are timestamped, tamper-evident, access-controlled, and audit-trailed. Metrolabs BMS T&H data logging is configured to meet all Part 11 electronic record requirements — data is admissible as GMP evidence in US-FDA, PMDA, and MHRA inspection submissions.

21 CFR Part 11

NABL & FSSAI

NABL ISO/IEC 17025 accreditation and FSSAI licensing require documented evidence of controlled temperature and humidity conditions in test and production areas. Metrolabs T&H logging with NIST-traceable sensor calibration provides continuous, documented compliance evidence for both accreditation bodies.

NABL · FSSAI · IEC 60751
Commission Your T&H Control System

Ready to Achieve ±0.3°C and ±2% RH with 21 CFR Logging?

Contact Metrolabs for a free consultation. Our instrumentation specialists will assess your AHU configuration, zone layout, regulatory requirements, and BMS platform — then specify, supply, install, commission, and tune a complete PLC-PID T&H control system with sensor calibration certificates and 21 CFR Part 11 data logging at handover.

🌡️
±0.3°C — PID Precision — No Hunting
PT100/PT1000 + PLC PID tuned per AHU — smooth, stable setpoint
💧
±2% RH — Capacitive Sensor — Coordinated
Dual-channel coordinated cascade — no T/RH interaction hunting
📋
21 CFR Part 11 — Audit-Ready from Day 1
Timestamped, tamper-evident BMS log — WHO/FDA/EU Annex 1 accepted
Modbus / BACnet / 4–20mA — Any BMS
Integrates with Siemens, Honeywell, Schneider or any BACnet/Modbus platform

🌡️ Request a Free T&H Controller Consultation

Consultation Requested!

Our T&H instrumentation team will contact you within 24 working hours.

Immediate: 9840931231